Note: For this tutorial, a running Proficy iFIX version 6.1 system is used and the SCU database and driver are changed to KEPServerEx version 6.11.718.

...

Outline of Steps:

  1. Download and Install KEPServerEX Video 1Preparing KEPServerEX for an iFIX PDB Connection

  2. Copy the IGS Driver Configuration File to the new KEPServerEX Configuration Utility

    1. Open the Industrial Gateway Server (IGS) Configurator

      Image Added
    2. Open KepServer/ Config File>

      Image Added
    3. Save as>

      Image Added
    4. input password or select no encryption and click OK.

      Image Added
    5. Save the .opf file from the IGS Config to desk top to Desktop with an IGS identifier i.e “IGS_CFG.opf”

      Image Added
    6. Close the IGS Configurator

      Image Added
    7. Open the KEPServerEX Configurator

      Image Added
    8. Open the file you just saved File>Open navigate to the desktop folder

      Image Added
    9. Click “Yes, Update”

      Image Added
    10. Close KEPServerEX

      Image Added
  3. Add the IDS Driver for the SCU (System Configuration Utility)

  4. Open iFix then the Database Manager>

    1. Export

      Database

      db_IGS.csv >

    2. Open with

      Navigate to the file in the File Elpolrer>Open with… Wordpad>

    3. Modify>ctrl H find and replace ,”IGS”, with ,”IDS”,

    4. save as IDS_

      Database

      db.csv >

    5. close wordpad

    6. Load Empty Database then

    7. Import new IDS_

      Database

      db

    8. verify tags are updating> Ctrl+R

    9. Update the Database Path in SCU

  5. Restart iFix

    1. Verify the Tags are connected via the new KEPware /IDS Driver Quick Client

    2. Delete the IGS driver from the SCU

Widget Connector
overlayyoutube
_templatecom/atlassian/confluence/extra/widgetconnector/templates/youtube.vm
width400px
urlhttps://www.youtube.com/watch?v=VF2L_MaGFSU
height300px

The configuration that is in your IGS file

...

Info

Before we get started you need:

In order for IDS components to be installed, iFIX software must be installed before KEPServerEX.

  1. Open the KEPServerEX project. Then, click File | Project Properties.

  2. Select the iFIX PDB Settings tab and then check Enable connectivity to iFIX PDB.

  3. Leave the remaining fields at their default settings and click OK.

Overview and Requirements

...

  1. Users must install Proficy iFIX before installing KEPServerEX, because files are installed to it in
    addition to the server.

  2. Double-click on the KEPServerEX icon and select Run or Open to start the install. If an
    active content warning is displayed, click “Yes” to continue.

  3. In the installation welcome screen, click Next.

  4. In End-User License Agreement, click I accept the terms in the License Agreement.
    Click Next.

  5. Continue through the installation, changing the settings as desired.

  6. In Select Complete Features, expand the driver tree in order to view and select the drivers desired
    for install. Then, expand Native Client Interfaces.

  7. Open the GE iFIX Native Interface drop-down menu and select Will be installed on local hard drive. Click Next.

  8. Click Install to start the installation.

...

  • Configure the KEPServerEX application.

  • Start KEPServerEX and load the Simulation Driver Demo project. Once the server
    project has been loaded, open the Runtime menu on the main menu bar and verify that
    the server project has been connected.

In order for IDS components to be installed, iFIX software must be installed before KEPServerEX.

  1. Open the KEPServerEX project. Then, click File | Project Properties.

  2. Select the iFIX PDB Settings tab and then check Enable connectivity to iFIX PDB.

  3. Leave the remaining fields at their default settings and click OK.

Info

Note: For more information on the tab's parameters, click Help

Connecting to the Server from iFIX

  1. Open the Proficy iFIX Startup menu and click Run the System Configuration Utility.

  2. Click the SCADA Configuration icon located in the bottom of the SCU - FIX window.

    1. picture

  3. Under Scada Support, select Enable to activate the Database Definition and the I/O Driver
    Definition dialog sections

  4. Under Database Definition, accept the default database name "DATABASE." Click the I/O Driver Name browse button. In the list of available drivers, select IDS – Industrial Data Server and then click OK.

...

  1. In order to receive data from the server, tags must be added to iFIX. In Proficy iFIX Startup,
    launch Proficy iFIX.

  2. In the Proficy iFIX workspace, expand the Database folder in the project tree and doubleclick Database Manager.

  3. In Welcome to Proficy iFIX Database, click to select Open Local Node, then click OK

  4. In the Proficy iFix Database Manager, all of your should be showing IGS in the I/O Dev column press F3

    1. (Ctrl+R) to Refresh the the data and you can see that the data is updating.

    1. Image Removed

    2. We are assuming that you are online with the PLCs if you are not the I/O address will show “????”

    3. Image Added

  5. Click the Export within the group of Blocks icons. Export the Database as a .CSV (copy the location in the file explorer). Save as “Filename”IGS

  6. Open the File Explorer paste the path where the Database was saved. Right click on the .csv file ans select Open with and select Wordpad.

  7. pic

  8. Use Ctrl+H to open a find and replace dialog box in the find field input ,”IGS”, in the replace input ,”IDS”,
    Save as IDS“Filename”

  9. Update the Database Path in SCU

  10. Open KEpServerEX Make sure the startup database name has updated to the new Database file name SCU “IDS_filename”

  11. Open KEPServerEX verify the connection

  12. Restart iFix Verify the Tags are connected via the new IDS Driver Quick Client

  13. Delete the IGS driver from the SCU

...