Note: For this tutorial, a running Proficy iFIX version 6.1 system is used and the SCU database and driver are changed to KEPServerEx version 6.11.718.
...
Outline of Steps:
Download and Install KEPServerEX Video 1Preparing KEPServerEX for an iFIX PDB ConnectionCopy the IGS Driver Configuration File to the new KEPServerEX Configuration Utility
Open the Industrial Gateway Server (IGS) Configurator
Open KepServer/ Config File>
Save as>
input password or select no encryption and click OK.
Save the .opf file from the IGS Config to desk top to Desktop with an IGS identifier i.e “IGS_CFG.opf”
Close the IGS Configurator
Open the KEPServerEX Configurator
Open the file you just saved File>Open navigate to the desktop folder
Click “Yes, Update”
Close KEPServerEX
Add the IDS Driver for the SCU (System Configuration Utility)
Open iFix then the Database Manager>
Export
Databasedb_IGS.csv >
- Open with
Navigate to the file in the File Elpolrer>Open with… Wordpad>
Modify>ctrl H find and replace ,”IGS”, with ,”IDS”,
save as IDS_
Databasedb.csv >
close wordpad
Load Empty Database then
Import new IDS_
Databasedb
verify tags are updating> Ctrl+R
Update the Database Path in SCU
Restart iFix
Verify the Tags are connected via the new KEPware /IDS Driver Quick Client
Delete the IGS driver from the SCU
Widget Connector | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
|
The configuration that is in your IGS file
...
Info |
---|
Before we get started you need: In order for IDS components to be installed, iFIX software must be installed before KEPServerEX.
|
Overview and Requirements
...
Users must install Proficy iFIX before installing KEPServerEX, because files are installed to it in
addition to the server.Double-click on the KEPServerEX icon and select Run or Open to start the install. If an
active content warning is displayed, click “Yes” to continue.In the installation welcome screen, click Next.
In End-User License Agreement, click I accept the terms in the License Agreement.
Click Next.Continue through the installation, changing the settings as desired.
In Select Complete Features, expand the driver tree in order to view and select the drivers desired
for install. Then, expand Native Client Interfaces.Open the GE iFIX Native Interface drop-down menu and select Will be installed on local hard drive. Click Next.
Click Install to start the installation.
...
Configure the KEPServerEX application.
Start KEPServerEX and load the Simulation Driver Demo project. Once the server
project has been loaded, open the Runtime menu on the main menu bar and verify that
the server project has been connected.
In order for IDS components to be installed, iFIX software must be installed before KEPServerEX.
Open the KEPServerEX project. Then, click File | Project Properties.
Select the iFIX PDB Settings tab and then check Enable connectivity to iFIX PDB.
Leave the remaining fields at their default settings and click OK.
Info |
---|
Note: For more information on the tab's parameters, click Help |
Connecting to the Server from iFIX
Open the Proficy iFIX Startup menu and click Run the System Configuration Utility.
Click the SCADA Configuration icon located in the bottom of the SCU - FIX window.
picture
Under Scada Support, select Enable to activate the Database Definition and the I/O Driver
Definition dialog sectionsUnder Database Definition, accept the default database name "DATABASE." Click the I/O Driver Name browse button. In the list of available drivers, select IDS – Industrial Data Server and then click OK.
...
In order to receive data from the server, tags must be added to iFIX. In Proficy iFIX Startup,
launch Proficy iFIX.In the Proficy iFIX workspace, expand the Database folder in the project tree and doubleclick Database Manager.
In Welcome to Proficy iFIX Database, click to select Open Local Node, then click OK
In the Proficy iFix Database Manager, all of your should be showing IGS in the I/O Dev column press F3
(Ctrl+R) to Refresh the the data and you can see that the data is updating.
We are assuming that you are online with the PLCs if you are not the I/O address will show “????”
Click the Export within the group of Blocks icons. Export the Database as a .CSV (copy the location in the file explorer). Save as “Filename”IGS
Open the File Explorer paste the path where the Database was saved. Right click on the .csv file ans select Open with and select Wordpad.
pic
Use Ctrl+H to open a find and replace dialog box in the find field input ,”IGS”, in the replace input ,”IDS”,
Save as IDS“Filename”Update the Database Path in SCU
Open KEpServerEX Make sure the startup database name has updated to the new Database file name SCU “IDS_filename”
Open KEPServerEX verify the connection
Restart iFix Verify the Tags are connected via the new IDS Driver Quick Client
Delete the IGS driver from the SCU
...