Download and Install KEPServerEX Video 1Copy the IGS Driver Configuration File to the new KEPServerEX Configuration Utility
Open the Industrial Gateway Server (IGS) Configurator
Open KepServer/ Config File>
Save as>
input password or select no encryption and click OK.
Save the .opf file from the IGS Config to desk top to Desktop with an IGS identifier i.e “IGS_CFG.opf”
Close the IGS Configurator
Open the KEPServerEX Configurator
Open the file you just saved File>Open navigate to the desktop folder
Click “Yes, Update”
Close KEPServerEX
Add the IDS Driver for the iFIX SCU (System Configuration Utility)
Open the iFix program
Use Ctrl + W to toggle from Run mode to Configure mode
Navigate to Applications then SCU to open the System Configuration Utility
Navigate to Configure>SCADA
On the SCADA Configuration page click the ellipsis…> Select IDS- Industrial Data Server> then OK
Click Add> Now you will see IDS listed under Configured I/O Drivers > Click OK
Now IDS appears on the SCU Terminal window (you can navigate File> Save) or just minimize for now
Modify the
Open iFix Workspace then the Database Manager>
The Welcome to iFIX Databas… Select > Open Local Node> OK
When the database first opens current value may be “????” refresh the database connection Ctrl+R
verify the database is updating Current Values
Verify the tags are using the IGS Driver
Select Export on the Home row of icons
Export db_IGS.csv We recommend that you rename the database “filename_IGS.csv” select Save
>
Navigate to the file in the File Elpolrer>Open Explorer >Open with… Wordpad>
Modify>ctrl H find and replace ,”IGS”, with ,”IDS”,
save as IDS_db.csv >
close wordpad
Load Empty Database then
Import new IDS_db
verify tags are updating> Ctrl+R
Update the Database Path in SCU
Restart iFix
Verify the Tags are connected via the new KEPware /IDS Driver Quick Client
Delete the IGS driver from the SCU
...