Field

What to Monitor

Est. Days to Full

If time is growing short, make sure that the server has sufficient unused storage capacity to open a new archive when the active one fills up. Verify that the Create New Archives Automatically function is enabled. If it is disabled, you must manually create a new archive before the active archive fills up. If you do not have enough unused storage capacity, you may have to enable the Overwrite Old Archives feature. Since this feature overwrites existing data, exercise caution in using it.

Consumption Rate of Archive Storage

If the rate is excessively high, you must either reduce the rate at which data flows into the system or increase the filtering applied to the data to lower the rate of archiving. To reduce the collection rate, slow the polling rate on some or all tags. To increase filtering, enable compression at the collector and/or archiver and widen the compression deadbands.

Failed Writes

If the display shows a significant number of failed writes, investigate the cause and take corrective action to eliminate the malfunctions. Refer to the DataArchiver-XX.log file or query the message database to determine the tags for which failed writes occurred.For example, trying to write values to a deleted archive causes failed writes. Trying to archive data with a timestamp that precedes the start time of the first archive, trying to write to a read-only archive, or trying to write a value with a timestamp more than 15 minutes ahead of the current time on an archiver will produce a failed write.

System Alerts

Examine the messages and alerts and take appropriate action to correct any problems.

Collector Performance Indicators (see Collector Maintenance, Performance Tab)

Avg. Event Rate Chart – is the rate at a normal level?

Performance Tab):·         Avg. Event Rate Chart·         Chart, Compression Chart·         Chart, Overruns Chart

Does the chart exhibit an acceptable trend line? If not, determine why. Balance polling schedules, adjust scan frequencies (collection intervals), and modify compression deadbands to lighten load. Compression Chart – is compression effectiveness acceptable? If not, verify that compression is enabled and then widen the deadbands to increase the effect of compression.Overruns Chart – if the value is anything other than zero, determine the severity and cause of the problem and take corrective action.

...