What communications (TCP/UDP) ports do GE Proficy products use?
For Cimplicity, please refer to :
https://digitalsupport.ge.com/communities/en_US/Article/What-Communications-TCP-UDP-Ports-Does-CIMPLICITY-UseB8442
For Plant Application, please refer to:
https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Application-Suite-Port-Firewall-Requirements-Plant-Applications-SOA-Workflow-Vision-Historia
IP Port | Product | Usage | Modifiable |
53014 | iFIX | PDB Synchronization - UDP | No |
2010 | iFIX | iFIX Networking (Including FIX) - TCP | No |
13000 | Historian | WCF network to Data Archiver | Yes, KB16244 |
14000 | Historian | Historian Collector, ClientManager (Mirror System), Remote Collector Management Agent | Yes, KB16245 |
14001 | Historian | Data Archiver (Mirror System) | No |
14003 | Historian | DiagnosticsManager (Mirror System) | No |
491 | Webspace | Proficy WebSpace Server accepts connections | Yes, KB16055 |
492 | Webspace | “Proficy WebSpace Relay Client Manager Service" to centrally manage the WebSpace user count in a Relay Server configuration. | No |
2101 | IGS | Ethernet Encapsulation | Yes, Property window |
4840 | IGS | OPC UA Client - Local Discovery Service | No |
49310 | IGS | OPC UA Server | Yes, 000019505 |
3333 | Common Licensing | Used to connect Local License Server | Yes, 000033940 |
443 | Common Licensing | Used to connect GE Cloud License Server | No |
443 | WEB HMI | External GE Web HMI clients to connect to GE Web HMI. | Yes, 000033822 |