  1. Download and Install KEPServerEX

  2. Copy the IGS Driver Configuration File to the new KEPServerEX Configuration Utility

    1. Open the Industrial Gateway Server (IGS) Configurator

    2. Open KepServer/ Config File>

    3. Save as>

    4. input password or select no encryption and click OK.

    5. Save the .opf file from the IGS Config to desk top to Desktop with an IGS identifier i.e “IGS_CFG.opf”

    6. Close the IGS Configurator

    7. Open the KEPServerEX Configurator

    8. Open the file you just saved File>Open navigate to the desktop folder

    9. Click “Yes, Update”

    10. Close KEPServerEX

  3. Add the IDS Driver for the iFIX SCU (System Configuration Utility)

    1. Open the iFix program

    2. Use Ctrl + W to toggle from Run mode to Configure mode

    3. Navigate to Applications then SCU to open the System Configuration Utility

    4. Navigate to Configure>SCADA

    5. On the SCADA Configuration page click the ellipsis…> Select IDS- Industrial Data Server> then OK

    6. Click Add> Now you will see IDS listed under Configured I/O Drivers > Click OK

    7. Now IDS appears on the SCU Terminal window (you can navigate File> Save) or just minimize for now

  4. Modify the current tag database

    1. Open iFix Workspace then the Database Manager>

    2. The Welcome to iFIX Databas… Select > Open Local Node> OK

    3. When the database first opens current value may be “????” refresh the database connection. Refresh the connection with: Ctrl+R

      1. verify the database is updating Current Values

      2. Verify the tags are using the IGS Driver

      3. Select Export on the Home row of icons

    4. Export db_IGS.csv We recommend that you rename the database “IGS_filename.csv” select Save

    5. Navigate to the file

      1. in the File Explorer C:\Program Files (x86)\GE\iFix|PDB

      2. right click>Open with… Notepad>

    6. Modify the IGS .csv file

      1. >Ctrl H to open Find and Replace

      2. in the “Find what:” field type ,”IGS”, In the “Replace with:” field type ,”IDS”, Select Replace All

      3. Close the Replace dialog box with Cancel. Notice IGS is now IDS

    7. From Notepad File> Save as

    8. In the Save As dialog box change the File name to db_IDS.csv and click Save

    9. close Notepad

    10. Return to the Database Manager and click the “Load Empty” icon on the Navigation bar then

    11. With a blank database click the “Import” icon select the new IDS_db.csv file. NOTE: When the Scan Alarm and Control database is stopped all iFIX data fields will show ????

      1. Click OK

      2. Select the newly modified filename_IDS.csv

    12. The size of your database will impact how long this takes. Luckily there is a Progress bar to stare at.

    13. After the new database populates verify the I/O Dev type

      Image Added
    14. verify tags are updating> Ctrl+R

      Image Added
    15. Use the Save As icon on the very top ribbon to Rename the new database to filename_IDS.

      Image Added
    16. Image Added
  5. Update the Database Path in SCU> Save

    1. Open up the SCADA Configuration in the SCU > Configure> SCADA

      Image Added
    2. In the SCADA Configuration menu, notice the Database Definition in this example is still _IGS.

      Image Added
    3. Select the ellipsis to update to the new IDS database you created in step 4. Select Open

      Image Added
    4. Verify the Database Definition is updated to _IDS click Ok to close the SCADA Configuration

      Image Added
    5. From the SCU Navigate to File> Save> Yes. Then you can close the SCU. If you try to close the SCU before Saving your changes you will be prompted to Save.

      Image Added
    6. Image Added
  6. Shutdown and Restart iFix

    1. Close all of the iFIX tabs until all you have open is the Startup Utility.

    2. Under Options select Shutdown iFIX. This will take a minute to stop all of the background processes.

      Image Added
    3. Double-click on your iFIX desktop shortcut to launch a new instance. You can open up the SCU and verify the Database Definition or open iFIX

      Image Added
  7. Verify the Tags are connected to your graphics or via the new KEPware /IDS Driver Quick Client

    1. Image Added
  8. Delete the IGS driver from the SCU

    1. Open the SCU

...

    1. > Confiiguration > SCADA

      1. Image Added
    2. Image Added

...

Info

Before we get started you need:

In order for IDS components to be installed, iFIX software must be installed before KEPServerEX.

  1. Open the KEPServerEX project. Then, click File | Project Properties.

  2. Select the iFIX PDB Settings tab and then check Enable connectivity to iFIX PDB.

  3. Leave the remaining fields at their default settings and click OK.

...